W8087S Ammonia Nitrogen Monitor

Short Description:


Product Detail

Product Tags

The  industrial  online  ammonia nitrogen monitor is an online water quality   monitoring   and   control instrument with a microprocessor. This instrument  is equipped with various types of ion electrodes and is widely used in power plants, petrochemicals, metallurgy    electronics,    mining, papermaking,  biological  fermentation engineering, medicine, food and beverage, environmental     protection     water treatment, etc. It continuously monitors and  controls  the  ion  concentration values of water solutions.

Instrument features:

 Large LCD screen liquid crystal display

 Intelligent menu operation

 Historical data recording

 Various automatic calibration functions

 Differential signal measurement mode, stable and reliable

 

  Manual      and       automatic      temperature compensation

Three groups of relay control switches

Upper limit, lower limit, hysteresis control

Multiple output methods including 4-20mA and RS485

 Display   of   ion   concentration,   temperature, current, etc. on the same interface

 Password    setting     for    protection     against unauthorized operation by non-staff members

 

 

 

 

 

Techn ical specificat ion

(1) Measurement  range  (based  on  electrode range):

Ion concentration (NH4+): 0.02 - 18000 mg/L (Solution pH value: 4 - 10 pH);

Compensated  ion  concentration  (K+):  0.04  - 39000 mg/L

(Solution pH value: 2 - 12 pH);

Temperature: -10 - 150.0 ℃;

(2) Resolution:

Concentration: 0.01/0. 1/1 mg/L;

Temperature: 0.1 ℃;

(3) Basic error:

Concentration: ±5 -  10%  (based  on  electrode range);

Temperature: ±0.3 ℃;

(4) 2-channel current output:

0/4 – 20 mA (load resistance < 750 Ω);

20 – 4 mA (load resistance < 750 Ω);

(5) Communication output: RS485 MODBUS RTU;

(6) Three groups of relay control contacts: 5A 250VAC, 5A 30VDC;

(7) Power supply (optional):

85 – 265 VAC ± 10%, 50 ± 1 Hz, power ≤ 3 W; 9 - 36 VDC, power: ≤ 3 W;

(8) External dimensions: 144 × 144 × 118 mm;

(9)     Installation     method:     panel-mounted, wall-mounted, pipe-mounted;

Panel opening size: 137 × 137 mm;

(10) Protection level: IP65;

(11) Instrument weight: 0.8 kg;

(12) Instrument working environment: Ambient temperature: -10 - 60 ℃;

Relative humidity: not more than 90%;

No  strong  magnetic  field  interference  except for the Earth’s magnetic field.